Typical Parrott Shielding Door Specifications
Parrott Shielding
SPECIFICATION
SECTION - NEUTRON SHIELDED DOOR
PART 1 – GENERAL
DESCRIPTION:
The work of this section consists of furnishing and
installing the door and furnishing only the frame.
PART 2 – PRODUCTS
MANUFACTURER:
Neutron shielded door and frame shall be as manufactured
by Parrott Shielding 101 1/2 North
Phone:(502)778-6737
Fax:(502)778-6909.
DOOR AND FRAME:
The door shall be constructed of 1/2” steel framing
member around the entire perimeter of door and shall have 1/4” steel
faceplates.
All weld joints shall be ground smooth. The hinge faceplates of the door shall have
1/2” x size required bar stock welded to the interior of the plate diagonally,
the full length of the door.
The interior of the door shall have lead shielding and
polyethylene, as indicated on drawings.
The door and frame shall be pre-finished in shop primer.
Frame shall be constructed of 1/4” steel of shape and
size as detailed on architectural drawings, complete with bottom lead lined
sill as shown and
welded in anchors including sill
anchors.
The face of the hinge jamb of the frame shall be
reinforced the full length with 3/4” bar reinforcing as shown.
The header of the frame shall be reinforced and prepared
for the all-electric operator and all necessary conduit openings and kill
switch preparation.
HARDWARE:
The Hardware shall include the following items to be
furnished and installed by the door manufacturer:
Pivot/Hinge
Furnish two (2) triple weight concealed ball-bearing
pivots/hinges capable of carrying the weight to be determined per pair of
pivots/hinges per door leaf.
Pivot/hinge leaves shall be applied to door and frame
with 1/2” allen head machine
screws.
Pulls
Furnish two (2) cast bronze heavy-duty pulls #2 for each
door US26D finish.
Electric Operator
Furnish all electric self-contained automatic door operator with spring-open/power closing features. The operator shall be free-egress in case of
power failure.
Furnish (2) push button stations with press-to-open,
press-to-close features. Conduits and
wiring shall be furnished under Division 16.
The operator will be
installed by the local
representative with coordination of the installation by Parrott Shielding.
Kill Switch (Interlock)
Furnish two (2) kill switches in hinge jamb of door frame
to interrupt power to accelerator when door is not in fully closed position.
INSTALLATION:
Door shall be field installed by Parrott Shielding along
with all hardware. Frame to be furnished by Parrott Shielding, but installed by
general works contractor.